In the control loop of low-voltage electrical appliances, there are simple low-voltage components such as buttons, insurance, etc.; there are also slightly more complex low-voltage electrical control components, such as circuit breakers, contactors, time relays, thermal relays and other simple components, which are necessary for faults. Diagnosis and analysis of causes. According to the characteristics of low-voltage electrical appliances, this paper mainly combines the three main types of low-voltage electrical appliances, namely vacuum circuit breakers, contactors and relays, to analyze the causes of their failures, and discuss the current technical methods and means of low-voltage electrical testing, in order to share with peers.
Commonly used low-voltage electrical fault diagnosis
Vacuum circuit breaker
As a new type of circuit breaker, the vacuum circuit breaker has many advantages compared with the previous oil-less circuit breakers and magnetic blown circuit breakers. Especially in recent years, the influx of the latest foreign vacuum circuit breakers and the continuous innovation of domestic manufacturers make Compared with the past, the structure of vacuum circuit breaker has undergone major changes, so that many workers will find it difficult to use, maintain and maintain the new vacuum circuit breaker, especially if there is a failure, they are helpless.
Whether the vacuum circuit breaker is faulty, it can be judged according to whether it can be closed and opened accurately and reliably and kept in the closed and open positions. Faults in the main circuit can be found and eliminated from the routine inspection and maintenance of the circuit breaker.
The main common failure causes are as follows:
cannot store energy. Inability to store energy is one of the more common faults of vacuum circuit breakers, especially the energy storage mechanism driven by ratchet wheels and pawls, which has a higher probability of failure. The energy storage mechanism to complete the energy storage action mainly depends on the three links of the energy storage motor, the drive mechanism, and the positioning parts. Grasping these three links closely, it is easy to find the crux of the fault.
No closing action. The occurrence of a failure without closing action is mainly related to whether the closing electromagnet is attracted, whether the energy storage is in place, and whether the positioning member is operating normally.
空合. If there is a closing action but not closing, it is called a dry close. When analyzing this type of fault, we should first start with the analysis on the closing and holding (locking), and then analyze whether it is related to the energy storage part.
The gate does not open. It should be emphasized here that when the circuit breaker refuses to operate or closes, before analyzing and repairing the main body of the circuit breaker, it is necessary to fully judge whether the cause lies in the control and secondary components such as auxiliary switches, terminal blocks, etc., and then Carry out analysis and diagnosis of the circuit breaker.
contactor
Contactors are divided into AC connection, DC contactors, intermediate frequency contactors, AC vacuum contactors, etc. Among them, AC contactors are the most widely used. AC contactor is an electromagnetic automatic switch. It is mainly used for remote control of motors and other loads with large power and frequent starting. It is the most commonly used control electrical appliance in the power system; it can easily cause equipment and personal accidents when it fails. Try to rule out.
The common faults of AC contactors are that after the coil is energized, the contactor does not act or act abnormally, and after the coil is de-energized, the contactor does not release or delay release.
After the coil is energized, the contactor does not act or acts abnormally. The main reasons for the failure are:
The coil control circuit is open: check whether the wiring terminal is broken or loose, if there is a broken wire, replace the corresponding wire, if it is loose, tighten the corresponding wiring terminal.
The coil is damaged: Use a multimeter to measure the resistance of the coil. If the resistance is +∞, replace the coil.
The coil rated voltage is higher than the line voltage. Replace with a coil that adapts to the control line voltage.
After the coil is de-energized, the contactor does not release or releases after a delay. The main causes of failure are:
There is no air gap in the column of the magnetic system, and the remanence is too large. File a part of the pole face at the residual magnetic gap to make the gap 0.1~0.3mm, or connect a 0.1uF capacitor in parallel at the two ends of the coil.
The surface of the activated contactor core is oily or greasy after a period of use. Wipe clean the anti-rust grease on the surface of the iron core. The surface of the iron core must be flat, but it should not be over-lighted, otherwise it is easy to cause delayed release.
The contact has poor resistance to welding. When the motor is started or the circuit is short-circuited, the high current causes the contact to be welded firmly and cannot be released. Among them, the pure silver contact is easier to weld.
Relay
Relay is an automatic device that is responsible for the important task of ensuring the safe and reliable operation of the power system in the power system. It monitors the operating status of the system at any time, and can quickly find faults, and then selectively remove the faulty parts through the circuit breaker.
The common fault types and diagnosis analysis of relays are as follows:
Electrical corrosion of contacts. The load of contact switching is mostly inductive. At the moment when the inductive load is disconnected, its accumulated magnetic energy will generate a high back EMF at both ends of the contact, which will break down the air gap between the contacts to form sparks and cause electrical corrosion. Cause the contact surface to dent, cause poor contact, or stick the two contacts together and cannot be separated, thus causing a short circuit. Preventing electrical corrosion between the contacts can be achieved by setting up a resistance spark extinguishing circuit and a resistance-capacitance spark extinguishing circuit.
Dust on the contacts. Dust and dirt will deposit on the contacts of the relay, which will cause a black oxide film to form on the surface of the contacts, resulting in poor contact of the relay. Therefore, the contacts need to be cleaned regularly. Carbon tetrachloride liquid can be used. Ensure good contact performance of the contacts.