When the transformer is overhauled, the on-load tap-changer has to go through the process of disassembly, inspection and reassembly. The overhaul items are as follows:
"Technology" What aspects should be paid attention to in the maintenance of transformer on-load tap-changer?
1. Check, maintain and debug the tap changer core hanging core.
2. Cleaning, leak detection and maintenance of the tap changer oil chamber.
3. Inspection, cleaning, refueling and maintenance of the drive mechanism
4. Inspection and maintenance of oil conservator and its accessories
5. Inspection, maintenance and calibration of oil flow control relay (or gas relay), overpressure relay and pressure relief device.
6. Inspection of automatic control devices.
7. Treatment of insulating oil in oil conservator and oil room
8. Inspection, maintenance and debugging of motor mechanism and other devices.
9. Check the sealing of all parts and deal with oil leakage.
10. Inspection, maintenance and debugging of electrical control circuits.
11. Check and debug the connection between the tap changer and the motor mechanism.
1. Main operating points of the on-load tap-changer
1. Installation of combined on-load tap-changer
(1) Unscrew the bolts that fix the switch head cover, then remove the switch head cover, and pay attention to protect the sealing gasket.
(2) Check whether the notch on the drive shaft of the diverter switch is aligned with the triangular mark on the support plate.
(3) Remove the locking piece of the position indicator plate, and then take off the tap position indicator plate.
(4) Remove the nut connecting the main body of the diverter switch and the support plate. Tie a suspension wire to the suspension wire of the diverter switch, and carefully lift the main body of the diverter switch vertically. After hanging out of the oil chamber, place it on a platform or flat ground covered with plastic sheeting.
(5) Remove the oil suction pipe and take it out of the oil chamber.
(6) Check whether the oil chamber of the diverter switch is clean. If it is not clean, it should be cleaned up.
(7) Use a special hanger plate across the oil chamber to make the support flange exert force so as to hang the tap changer. Then unscrew the connecting bolts of the intermediate flange and the supporting flange to separate the two.
(8) Gently lower the hanging plate until the support flange mounts the tap-changer on the bracket mounted on the body, then the fuel-saving tank can be lifted.
(9) After lifting the mailbox in the previous section, check the selector as follows:
1) Check whether the connecting wire (copper rod) of the selector and switch is loose.
2) Check whether the contact between the tap line and the selector static contact is good, and whether the pressure equalizing cover is complete.
3) Check whether the tap lead makes the bakelite strip of the selector subject to horizontal tension (the horizontal tension should be close to zero).
4) Check whether the contact line of the selector moving contact is located in the cylindrical part of the static contact, and the distance from the spherical part of the static contact is not less than 2mm.
(10) Connect a bridge to the fixed main arc contact and the fixed transition contact or use a multimeter to measure the resistance value of the transition resistance. The deviation between the measured value and the nominal value on the nameplate should be within ±10%.
(11) After the upper fuel tank is reinstalled, the oil chamber of the diverter switch should be checked and cleaned again, rinsed with clean oil, and then the oil suction pipe should be installed.
(12) Lift the tap-changer with a special hanging plate, restore the connection between the intermediate flange and the supporting flange, and make the seal well.
(13) Lift the switch and carefully drop it into the oil chamber. In order to ensure the fit of the coupling, the insulating shaft of the diverter switch should be turned gently to insert the coupling and allow the diverter switch to fall into place.
(14) Reinstall the nuts of the fixing bolts on the support plate, and fix the switch to the support plate.
(15) Reinstall the position indicator plate and install the shaft head locking plate.
(16) Reinstall the switch head cover, tighten all the bolts on the switch head cover, make it firmly connected with the switch head flange, and ensure a good seal.
(17) A bypass pipe is installed on the oil return pipe on the flange of the switch head and the pipe joint connecting the oil tank of the transformer, so that the oil chamber of the switch switch is communicated with the inside of the oil tank of the transformer, so that the oil chamber and the oil tank can be filled with vacuum oil at the same time. When vacuum oil is poured into the bleed plug on the cover of the switch head, the bypass pipe should be removed, the sealing plate should be added, and then the vacuum oiling should be continued.
(18) Install the worm gear box and the bevel gear box, install the horizontal shaft and the vertical transmission shaft with the coupling chuck, and install the rain cover.
(19) Switch between forward and reverse directions by manual operation, and check the symmetry of the transmission mechanism. If it is not symmetrical, the vertical drive shaft should be loosened and adjusted until the difference between the number of rotations of forward and reverse switching does not exceed one rotation.
(20) The switching operation is performed manually first, and then the switching operation is performed by the electric mechanism. Check that the tap indicator and motor-drive position indicator are in the same position at each tap position.
2. Installation of compound on-load tap-changer
Its characteristics are that the direct switching selector switch and the switching switch are integrated, the oil in the tap changer tank is isolated from the transformer body oil, and the switching operation is completed at the same time as the tap selection, so the volume is large, because the voltage regulation is completed at one time, so the structure Simple, low cost, simple operation process, suitable for transformers with low current and low voltage, generally used on on-load voltage regulating transformers with fewer voltage taps (mostly 7 stages). The steps to install the compound on-load tap-changer are as follows:
(1) Adjust the tap position to the rated tap position.
(2) Remove the switch head cover, drain oil or air before removing
(3) Loosen the joint nut of the elbow of the suction pipe.
(4) Move the fitting body of the counter into the switch head.
(5) Remove the locking screw of the gear mechanism from the switch head and loosen the spring.
(6) Remember the position mark of the gear mechanism, remove the fixing screw of the gear mechanism, and then pull up the gear mechanism. Record the position of the support bar.
(7) Remove the oil suction pipe. When pulling out, first insert a screwdriver into the previous notch, pry up the oil suction pipe, then grab the second notch with your hand and pull out the oil suction pipe.
(8) Fix the special spreader to the coupling end face of the main body of the selector switch with 3 screws, and the stop baffle of the spreader must be inserted into the junction in the middle of the support crossbar.
(9) Twist the spreader clockwise so that the moving contact of the selector is located between the two phases, that is, at its lifting position.
(10) Hang the hanging object on the spreader, and pull out the selector switch body slowly and carefully. During the pulling process, pay attention to keeping enough clearance between the moving contact, the pressure equalizing ring and the oil chamber to avoid collision.
(11) Place the main body of the selector switch at the inspection location for inspection and cleaning.
(12) Screw the four M8 screws on the special tool of the oil hoisting chamber into the screw holes of the support flange. Hang the oil chamber, remove the bolts with locking washers connecting the support flange and the switch head flange, and then place the oil chamber on the support plate on the clamping line. At this point, the upper fuel tank can be lifted.
(13) After cleaning the oil chamber, reassemble it according to the above reverse procedure. However, the following points should be noted:
1) After inserting the oil suction pipe, press the top of the oil suction pipe firmly so that the main body of the selector switch is coaxial with the oil chamber.
2) Use the spreader to twist the switch to the calibration position.
3) The gear mechanism should be adjusted to the correct position, so that it can be inserted and coupled with the main body of the selector switch.
4) Before placing the switch head cover, put the sealing gasket first to ensure that the head cover is sealed.
5) Finally, cover the inspection window from the switch head to check whether it is the calibration position.
(14) Install the bypass pipe so that the oil chamber and the oil tank can be filled with oil at the same time, and at the same time install the drive shaft and the rain cover
(15) Check the symmetry of the transmission mechanism.
(16) Trial operation
Second, the installation inspection and adjustment of the tap changer
(1) Check the various components of the tap changer, including the diverter switch or selector switch, tap selector, changeover selector, etc. for damage and deformation.
(2) Check the insulating parts of the tap changer, there should be no cracking, creepage and damp phenomenon.
(3) Check that the fasteners of each part of the tap changer should be well tightened.
(4) Check that the contacts of the tap changer and their connections should be intact, in good contact, and connected correctly and firmly. If necessary, measure the contact resistance and the contact pressure and stroke of the contacts. Check that the copper braided wire should have no broken strands.
(5) Check whether the transition resistance is broken or loose, and measure the transition resistance value, and its resistance value should meet the requirements.
(6) Check the insulation distance of each part of the tap lead.
(7) The length of the tap lead should be suitable so that the tap changer is not subject to tension.
(8) Check that the valve between the decomposition switch and its oil conservator should be opened.
(9) Check the tap changer seal. When the transformer body and its oil conservator are filled with oil, drain the insulating oil in the oil chamber of the tap changer, check whether there is leakage in the oil chamber, and finally carry out the overall sealing inspection, including accessories and all pipes, there should be no leakage. Oil leakage phenomenon.
(10) Clean the oil chamber and core of the tap changer, inject insulating oil that meets the standard, and the oil level of the oil conservator should be adapted to the ambient temperature.
(11) When the transformer is evacuated, the tap changer oil chamber should be connected to the transformer itself. When the tap changer is used for vacuum oil filling, the transformer body and the tap changer oil chamber must be evacuated at the same time. For tap-changers with explosion-proof diaphragm, the explosion-proof diaphragm should be removed and replaced with a sealing plate. If the tap-changer oil conservator cannot withstand this vacuum value, the pipeline leading to the oil conservator should be removed, and all valves and venting plugs that affect the vacuum should be closed. When the tap changer is used for atmospheric pressure oil filling, an air outlet should be reserved to prevent the pressure release device from being swelled.